The magnetics behind every power converter
Almost every power converter contains a magnetic part: an inductor, a transformer, or a motor. This module builds the minimum background you need to understand them: magnetic circuits, induced voltage, AC power, three-phase systems, and transformers. Each page is short, and each idea comes with a live lab.
By the end you can
1. Use MMF, flux, and reluctance to find the inductance of a cored coil, and explain why air gaps and saturation matter.
2. Use Faraday’s law to relate voltage, turns, flux, and frequency, and use F = B·i·l for the force on a wire.
3. Separate real, reactive, and apparent power, and read a power factor correctly.
4. Describe a balanced three-phase system and convert between line and phase quantities in wye (Y) and delta (Δ).
5. Analyze ideal and real single-phase transformers: turns ratio, reflected impedance, losses, regulation, efficiency.
6. Predict the voltage ratio and phase shift of a three-phase transformer connection, and use it to find the DC bus of a rectifier.
Three physical facts, three kinds of device
| Fact | Law | Devices | Where you will meet it |
|---|---|---|---|
| A current creates a magnetic field | Ampère | Inductor, electromagnet | The buck and boost inductor stores energy in its field |
| A changing magnetic flux creates a voltage | Faraday | Transformer, generator | Voltage scaling, isolation, inductor volt-second balance |
| A current in a magnetic field feels a force | Lorentz | Motor, relay | Motor drives, the load of many inverters |
Starting from zero?
You need Ohm’s law, series and parallel circuits, and the idea of a sine wave with an RMS value. Everything else is introduced here. Grey Refresher boxes recap background, and green Power electronics link boxes show why the idea matters later in the course.
How to use this module
Each tab has a short explanation, one or more live labs, and activities. Move any slider and every number and graph updates. Activities with a number to find have a Load these settings button so everyone starts from the same circuit, and a Check button that compares your answer with the model. Nothing is sent anywhere; your answers stay in this page, and the last tab gives you a summary you can copy.
Suggested path: follow the tabs in order. Magnetic circuits and induction explain inductors and transformers; AC power and three-phase give the language of the grid; the two transformer tabs combine everything; the “Putting it together” tab connects it to converters.
Magnetic circuits: current in, flux out
A coil of wire wrapped on an iron core is the building block of inductors, transformers, and motors. Treat the core like a “circuit” for flux and you can solve it with the same ideas as Ohm’s law.
Refresher: electric and magnetic fields
Electric fields come from charge; magnetic fields come from moving charge, that is, current. Both weaken with distance. Magnetic fields are hard to block, which is why iron cores are used to guide them. Flux lines always form closed loops.
The quantities
| Quantity | Symbol, unit | Meaning | Electric analogue |
|---|---|---|---|
| Magnetomotive force | MMF = N·i, A·turns | The “push” from N turns carrying current i | Voltage |
| Flux | φ, weber (Wb) | Total field lines through the core | Current |
| Reluctance | ℛ, A·turns/Wb | How hard the path resists flux | Resistance |
| Field intensity | H, A·turns/m | MMF per metre of path | Electric field |
| Flux density | B, tesla (Wb/m²) | Flux per unit area | Current density |
| Permeability | µ = µrµ0, H/m | How easily the material carries flux; µ0 = 4π×10−7 | Conductivity |
The last equation is “Ohm’s law for magnetics”. Reluctances in series add, just like resistances. Air has µr = 1 while iron may have 2 500 or more, so a thin air gap can dominate the total reluctance.
Inductance from the magnetic point of view
Inductance is flux linkage per amp: L = N φ/i. Substituting φ = N i/ℛ gives
Inductance grows with the square of the turns, with core area, and with permeability, and falls with path length and with any air gap.
Saturation
Iron cannot carry unlimited flux. Above roughly 1.5 to 2 T for silicon steel (0.3 to 0.5 T for ferrite), µ collapses toward µ0, ℛ jumps, and the inductance falls sharply. In a converter that means the current spikes. The lab includes saturation with Bsat = 1.6 T.
Lab: a cored coil with an air gap
Change the turns, current, core size, material, and gap. Watch where the MMF is spent: a small gap takes most of it.
Power electronics link
The inductor in a buck or boost converter is exactly this device. Its inductance sets the current ripple. Designers add an air gap on purpose, because the gap stores most of the energy and keeps the core out of saturation at the peak current. Transformers do the opposite: they use a closed core with no gap so that the flux links both windings.
Activities
Induced voltage and force
Ampère’s law says current makes flux. Faraday’s law is the reverse: changing flux makes voltage. Together with the force on a current-carrying wire, they explain transformers, generators, and motors.
Faraday’s law
The voltage induced in a coil equals the turns times the rate of change of the flux through it. The minus sign is Lenz’s law: the induced voltage would drive a current whose flux opposes the change. Only a changing flux induces voltage; constant flux induces nothing.
For a sinusoidal flux φ = Φm sin ωt, the voltage is e = N ω Φm cos ωt, a cosine that leads the flux by 90°. Its RMS value is
Lab: voltage from a changing flux
Three “actions”
| Action | What happens | Example |
|---|---|---|
| Transformer | A time-varying flux induces voltage in a stationary coil | Utility and converter transformers |
| Generator | A conductor moving through a field has voltage induced in it | Alternator, wind turbine |
| Motor | A current-carrying conductor in a field feels a force | Fan, EV traction motor, relay |
Force on a current-carrying wire
A wire of length l carrying current i in a field B feels a force
where θ is the angle between the wire and the field. The force is largest when the wire is perpendicular to the field, and its direction is given by the right-hand rule (index finger along the current, middle finger along B, thumb along F). A motor is a set of such wires on a rotor, so the force becomes torque.
Lab: force on a wire
Power electronics link: volt-seconds
Rearranging Faraday’s law gives φ = (1/N)∫v dt. The flux is set by the area under the voltage waveform, the volt-seconds. This is the same idea as inductor volt-second balance in a DC-DC converter: if the average voltage over a period is zero, the flux (and current) returns to where it started. It also explains why a transformer fed with half the frequency needs double the flux: you will see it in the “Putting it together” tab.
Activities
Real, reactive, and apparent power
With a DC source, power is just voltage times current. With AC, the current may be shifted in time from the voltage, and then not all of the volt-amps do useful work.
Refresher: RMS and phase
A sine of peak Vpk has RMS value Vpk/√2, the DC value that heats a resistor equally. Two sines of the same frequency can be shifted by an angle. For an inductive load the current lags the voltage (θ > 0); for a capacitive load the current leads (θ < 0).
The idea
Instantaneous power is always p = v i. If the current lags the voltage by θ, then p = V I cos θ + V I cos(2ωt − θ). The first term is constant; the second swings at twice the line frequency and averages to zero. Splitting it further:
| Power | Formula | Unit | Meaning |
|---|---|---|---|
| Real (active) | P = V I cos θ | W | Average power delivered to do work or make heat |
| Reactive | Q = V I sin θ | VAR | Energy stored and returned each cycle by L and C; does no net work |
| Apparent | S = V I | VA | What the source and wires must be rated for |
An inductive load consumes both P and Q. A capacitive load consumes P and supplies Q. Because cos(+30°) = cos(−30°), a power factor alone does not say whether the load is inductive or capacitive; always state “lagging” or “leading”.
Lab: waveforms and the power triangle
Power electronics link
Wires, switches, and transformers are limited by current, so they are rated in VA, not W. A low power factor wastes capacity. A simple diode rectifier with a capacitor draws narrow current pulses and has a poor power factor, which is why many converters add power-factor-correction (PFC) stages that make the input current follow the voltage.
Activities
Three-phase systems
Power is generated, transmitted, and used mostly as three-phase AC. Three voltages of equal size, 120° apart, give more power per kilogram of metal and a power flow that does not pulse.
Why three phases?
More power for the same copper. A three-phase system delivers more power per unit weight of conductor than a single-phase system, so lines, generators, and transformers are more compact.
Constant power. In single phase the instantaneous power pulses at twice the line frequency. In a balanced three-phase load the three pulsations add to a constant. This gives smooth torque in motors and a smooth DC output when the voltages are rectified.
Balanced sets and phase sequence
A balanced source has three voltages of equal magnitude and 120° apart; a balanced load has three equal impedances. Then the neutral current is zero, and the neutral wire is not needed. The phase sequence is the order in which the voltages reach their peaks. At the instant shown in the lab below, reading clockwise from A gives sequence ABC. Swapping two phases gives ACB, which reverses a motor’s direction.
Lab: rotating phasors and waveforms
Each phasor rotates counter-clockwise at the line frequency. The instantaneous voltage is its projection on the horizontal axis. Drag the angle, or press play, and notice that the three values always add to zero.
Wye and delta connections
Phase quantities are across or through one winding or load element. Line quantities are the line-to-line voltage and the current in a line conductor. For a balanced system:
| Wye (Y) | Delta (Δ) | |
|---|---|---|
| Voltage | VL = √3 Vφ | VL = Vφ |
| Current | IL = Iφ | IL = √3 Iφ |
| ABC sequence | Vab leads Van by 30° | Ia lags Iab by 30° |
| ACB sequence | Vab lags Van by 30° | Ia leads Iab by 30° |
Total power does not depend on the connection when written with line quantities:
where θ is the angle between the phase voltage and the phase current. Because the three phases are identical, you can analyze one phase (a per-phase circuit) and multiply by three.
Lab: balance, neutral current, and constant power
A four-wire wye system with resistive loads. Make phase C draw less current and watch the neutral current appear and the total power start to ripple.
Lab: wye or delta?
Connect the same three impedances in wye or delta on the same line voltage. The phasor diagram shows the √3 and the 30° shift.
Power electronics link
Three-phase diode and thyristor rectifiers, active front ends, and inverters all work from these relationships. The DC bus of a six-pulse rectifier is set by the line-to-line voltage, so you will often convert 208 V, 480 V, or 600 V line voltages to phase values (and back) while sizing a drive.
Activities
Ideal transformers
A transformer changes voltage and current levels using a shared magnetic flux. There is no electrical connection between the windings, only the core.
How it works
The same flux passes through both windings, so by Faraday’s law the voltage per turn is the same in each:
An ideal transformer has no losses, so power in equals power out, which forces the currents to scale the other way:
The turns ratio changes only the magnitudes, not the angles. Voltage and current keep the same phase on both sides.
Impedance reflection
A load ZL on the secondary looks, from the primary, like
This is why a transformer can “match” a load to a source, and why, in analysis, you move impedances across the transformer by multiplying or dividing by a2 and then delete the ideal transformer.
Dot convention
Dots tell you the polarity without looking at the winding direction. A voltage that is positive at the dotted end of one winding is positive at the dotted end of the other. A current entering the dot on the primary leaves the dot on the secondary, so N1i1 − N2i2 = 0.
Kinds of transformer
| By application | Role |
|---|---|
| Unit transformer | At a generator output; steps voltage up to transmission level |
| Substation transformer | Steps transmission voltage down to distribution level |
| Distribution transformer | Steps distribution voltage down to the use level (for example 120 V, 208 V, 240 V) |
| By function | What it does |
|---|---|
| Step-down | High voltage, low current in; low voltage, high current out (a doorbell runs from 120 V AC reduced to about 12 V) |
| Step-up | Low voltage, high current in; high voltage, low current out |
| Isolation | 1:1 ratio. No direct current path between sides, used for safety and noise control |
| Autotransformer | One winding with taps; part of the same winding is shared by primary and secondary. Smaller and cheaper, but no isolation |
Core construction is either core form (windings around two sides of a laminated rectangle) or shell form (a three-legged core with the windings on the center leg).
Lab: ideal transformer
Power electronics link
Isolated converters (flyback, forward, bridge types) put a high-frequency transformer between input and output for safety and for large voltage ratios. Utilities step voltage up for transmission because, for the same power, a higher voltage means a lower current and so far lower I2R loss in the line.
Activities
Real transformers: losses, regulation, efficiency
Real windings have resistance, not all flux links both windings, and the core wastes energy. A small equivalent circuit captures all of this.
Where the losses come from
| Effect | Cause | Depends on |
|---|---|---|
| Copper loss | Resistance of the windings | I2R: the load current |
| Eddy-current loss | Circulating currents in the core, which heat it | Rises with frequency; laminations or ferrite reduce it |
| Hysteresis loss | Magnetic domains reorienting every half-cycle | Frequency and peak flux density |
| Leakage flux | Some flux closes through air instead of linking both windings | Modeled as a series reactance |
Eddy and hysteresis losses together are the core loss. It is present whenever the transformer is energized, even with no load. Copper loss grows with the square of the load current.
The equivalent circuit
To analyze a circuit: reflect every impedance to the side where you need the answer (multiply or divide by a2), then remove the ideal transformer. The unknown voltage on the secondary is then found from a simple series circuit.
Here Rc represents core loss and Xm is the magnetizing reactance, the branch that carries the small current needed to set up the core flux.
Finding the parameters: two tests
Open-circuit test. Leave the secondary open and apply rated voltage to the other winding. Almost all the current is magnetizing current, and the power measured is the core loss. This gives Rc and Xm.
Short-circuit test. Short the secondary and raise the primary voltage from zero until rated current flows. The voltage is small, so the shunt branch is negligible, and the power measured is the copper loss. This gives Req and Xeq.
Lab: from test data to parameters
The transformer is 10 kVA, 2400/240 V. The open-circuit test is made on the 240 V side at rated voltage; the short-circuit test on the 2400 V side at its rated current of 4.167 A.
Voltage regulation and efficiency
A smaller VR means a stiffer output. A lagging (inductive) load makes the output droop. A leading (capacitive) load can make the secondary voltage rise, giving a negative VR. Efficiency peaks at the load where the copper loss equals the core loss.
Lab: regulation and efficiency of a 10 kVA, 2400/240 V transformer
The primary is held at rated voltage. Impedances are in percent (per unit × 100) on the transformer’s own rating.
Per-unit values
Instead of volts, amps, and ohms, engineers often divide each quantity by a base value. With a base power Sb and base voltage Vb:
A transformer’s per-unit impedance is the same whether you refer it to the primary or the secondary, so the ratio disappears from the calculation. Per-unit values also show at a glance whether an impedance is large or small. For a three-phase system use the three-phase Sb and the line-to-line Vb.
Ratings
The voltage rating protects the winding insulation, and also keeps the core out of saturation, so the voltage must be reduced if the frequency is reduced (“derating”). The current rating limits the I²R copper loss, which becomes heat. That is why transformers are rated in kVA: voltage limits the core, current limits the copper.
Activities
Three-phase transformers
Three transformer windings, either as three single-phase units or on one shared core, can be connected in wye or delta on each side. The choice changes the voltage ratio and can add a phase shift.
A three-phase unit is usually three windings on one core inside a tank of insulating oil. The oil insulates the windings from the case, carries heat away, and keeps out moisture. Compared with three separate single-phase units, it is lighter, cheaper, smaller, and slightly more efficient.
The primary and secondary can each be connected in Y or Δ, giving four combinations. Within one transformer the ratio of phase voltages is the turns ratio a, but the ratio of line voltages depends on the connections:
| Connection | Line-voltage ratio | Phase shift | Notes |
|---|---|---|---|
| Y–Y | a | 0° | Phase voltages can become badly unbalanced with unbalanced loads; third harmonics are a problem unless the neutrals are connected or a tertiary delta is used |
| Y–Δ | √3 a | 30° | Phase shift between primary and secondary |
| Δ–Y | a/√3 | 30° | Phase shift between primary and secondary |
| Δ–Δ | a | 0° | No phase shift, and tolerates unbalanced loads and harmonics |
Lab: connect the windings
Activities
Putting it together: from the grid to a DC bus
Two ideas from this module explain a lot about how power electronics is built: why switching at high frequency shrinks the magnetics, and how a transformer and a three-phase rectifier create the DC bus that feeds a DC-DC converter.
Why high frequency means small magnetics
Faraday’s law for a sinusoidal supply says V = 4.44 f N Bm Ac. Solving for the core area:
For a fixed voltage, turns, and flux density, the core area is inversely proportional to frequency. A 60 Hz iron transformer and a 100 kHz ferrite transformer for the same voltage differ enormously in size. The catch: eddy and hysteresis losses rise with frequency, and ferrite saturates at a lower Bm, so the gain is limited.
From three-phase AC to a DC bus
A six-pulse diode bridge connects the highest line-to-line voltage to the output at every instant. The average output is
so the transformer connection sets VL,sec, and that sets the DC bus feeding the converter. The transformer also provides isolation from the grid.
What comes next
| Concept from this module | Where it comes back |
|---|---|
| L = N²/ℛ, air gap, saturation | Inductor design in buck, boost, and buck-boost converters |
| Volt-seconds, e = N dφ/dt | Volt-second balance; transformer flux in forward and flyback converters |
| P, Q, S, power factor | Rectifier input current, PFC, converter ratings |
| Line and phase, √3, 30° | Three-phase rectifiers and inverters |
| Turns ratio, reflected impedance, losses | Isolated converters, efficiency estimates |
Activities
Check your understanding
Nine questions on the ideas from this module, then reflection prompts and a summary of your responses to copy.
Reflect
Save your work
This page does not store or send anything. To keep a record, or to turn it in if your instructor asks, build a summary below and copy it into your own document or email.
Formula reference
Magnetic circuits and induction
| Field intensity | H = N i/lc (A·turns/m) |
|---|---|
| Flux density, flux | B = µH, φ = B A, µ = µrµ0, µ0 = 4π×10−7 H/m |
| Reluctance | ℛ = l/(µA); series: ℛtot = ℛcore + ℛgap |
| MMF law | N i = φ ℛ |
| Inductance | L = Nφ/i = N2/ℛ |
| Faraday | e = −N dφ/dt; sinusoidal: Erms = 4.44 f N Φm |
| Force on a wire | F = B i l sin θ |
AC and three-phase power
| Single phase | P = VI cos θ, Q = VI sin θ, S = VI, PF = cos θ = P/S |
|---|---|
| With impedance | P = I2R, Q = I2X, S = I2Z |
| Wye | VL = √3 Vφ, IL = Iφ |
| Delta | VL = Vφ, IL = √3 Iφ |
| Three-phase total | P = √3 VLIL cos θ, Q = √3 VLIL sin θ, S = √3 VLIL |
Transformers
| Ideal | a = N1/N2 = v1/v2 = i2/i1, Zin = a2ZL |
|---|---|
| Open-circuit test | Rc = Voc2/Poc; Im = √(Ioc2 − (Poc/Voc)2); Xm = Voc/Im |
| Short-circuit test | Req = Psc/Isc2; Zeq = Vsc/Isc; Xeq = √(Zeq2 − Req2) |
| Regulation, efficiency | VR = (Vnl − Vfl)/Vfl; η = Pout/(Pout + Pcu + Pcore); max at Pcu = Pcore |
| Per unit | Zb = Vb2/Sb, Ib = Sb/Vb (1φ) or Sb/(√3Vb) (3φ) |
| 3-phase ratio | Y–Y, Δ–Δ: a; Y–Δ: √3a; Δ–Y: a/√3 (line-to-line, with a the winding turns ratio) |
| Core size | Ac = V/(4.44 f N Bm) |
| Six-pulse rectifier | Vdc = (3√2/π) VL ≈ 1.35 VL |